High energy secondary and basic primary level protection for large equipment and service entrances.

Surg-Patrol

Up to 500 KW systems, Category B & C locations.

The StediWatt Surg’Patrol Series is intended for heavy industrial, primary-level protection. It provides a safe, critical surge path direct to ground and isolates downline Category B environments from heavy surges, storm and utility line hazards. Ideal for hazard-prone areas where critical, system-dependent equipment or expensive downtime risk is a factor. This series is a must to provide a long-term internal protection grid and prevent serious power surging from entering your facility or sensitive equipment.

  • For 120VAC, Single Ø - up to 600VAC 3Ø Electrical Systems
  • MCOV Ratings: 150/320; 320/550; 420/750 VAC Max. (typ.)
  • Maintains SE* Single Element Surge Capacity: 80,000 Amps
  • Minimum Surge Current Per Phase: 160,000 Amps
  • Total Non-degrading Surge Capacity: 560,000 Amps
  • All Modes of Protection: L-L, L-N, L-G and N-G (if applies)
  • Leads are #10 Stranded Copper, Max 36" for Close-coupling
  • FuseLink Technology Maintains Full Rated Surge Capacity
  • User Safe, StediWatt Safety Surge Cushion™ *Patent Pending
  • UL and CUL Listed to Standard 1449, 2nd Edition
  • Safety tested to ANSI/IEEE C62.11,C62.41 & C62.45 Std. 587
  • Remote’Alert Provides Auto-remote Protection Status Alert*
  • LED Self-test Protection Status Monitors for each phase
  • Features Fiberglass NEMA Type 4X Rated Enclosures
  • Manufacturers 10 Year Full Replacement User Warranty
  • System Designed to Protect Downline TVSS From Degradation
Features New Robust, Hi-Energy “Single Element” (SE) TVSS design
500,000 Amps of Solid, Safe, Non-Degrading Lifetime Surge Capacity!
"Close Coupled" design assures safe, lightning fast response time for sensitive equipment
Affordable workhorse protection module for hazardous areas where downtime risks are mission critical
For primary-level, IEEE Category C Main Switch Gear, and critical surge-prone applications
Safely protects sensitive electrical equipment and total system load capacities up to 500KW systems
Greatly increases ‘Mean Time Between Failures’ of Lighting, Electronic and Electrical Equipment

Models

Model S-1120-3SP S-1208-4SP S-1240-3SP S-1240-4SP S-1480-3SP S-1480-4SP S-1600-3SP S-1600-4SP
AC Service Types 3Ø WYE 3Ø Delta 3Ø Hi-Leg 3Ø Delta 3Ø WYE 3Ø Delta 3Ø WYE
Nominal AC Line Voltage (VRMS) 120/240 120/208 240/240 120/208/240 480/480 277/480 600/600 347/600
Frequency Range - USA / Euro Std 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Single Element SE* Protection Modes L-N; L-L L-N; L-L & N-G L-L L-N; L-L & N-G L-L L-N; L-L & N-G L-L L-N; L-L & N-G
Knock Out Size for Mounting 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
Leads: #10 AWG Stranded Copper 3+G 4+G 3+G 4+G, Hi-Leg 3+G 4+G 3+G 4+G
Max. SE* Per Mode Surge KVA 80 80 80 80 80 80 80 80
Max. Surge Current Per Phase KVA 160 160 160 160 160 160 160 160
Total Surge Capacity (KVA@ 8x20 μsec pulse) 260 560 420 560 420 560 420 560
Max. Continuous Operating Voltage (MCOV) 150/320 150/320 320 150/320/320 550 320/550 680 390/680
Max. Clamping Voltage - L-L 520 520 520 520 1175 1175 1800 1800
Max. Clamping Voltage - L-N 390 390 N/A 390 N/A 675 N/A 1120
Max. Clamping Voltage - N-G 390 390 N/A 390 N/A 390 N/A 1120
Warranty 15 Years per Manufacturers Warranty Guidelines
Enclosure Dimensions (HxWxD) 8 1/4" X 6 1/4" X 4 1/4"
Enclosure Type NEMA/EEMAC Type 4X Waterproof, Explosion Proof, Spark Proof with Embeded PCB and Contacts
Certifications UL / CUL Std 1449, 3rd Edition and Full Line is ETL Certified, Safety Tested and Listed
Safety Testing UL & ANSI/IEEE C62.11,C62.41 & C62.45 Std. 587 and NEMA Std. LS-1
Protection Status Indicators Lifetime Green LED Self Test Indicators For Each Phase
Shipping Weight Lbs (Approx.) 8 8.5 8.5 8.5 8.5 8.5 9 9